DWYER OMEGA / MAGNEHELIC GAUGE NEAR DAMANGANGA INDUSTRIAL PARK VAPI GUJARAT

www.envirotechindia.info

DWYER OMEGA / MAGNEHELIC GAUGE NEAR DAMANGANGA INDUSTRIAL PARK VAPI GUJARAT

 

SERIES 2000 MAGNEHELIC® DIFFERENTIAL PRESSURE GAGES Indicate Positive,Negative or Differential, Accurate within 1%

  • No Power Required
  • Low Cost
  • Used in Isolation/ Hospital Environments and Temporary Units (no Power Required)

Select the Series 2000 Magnehelic® Gage for a versatile low Differential Pressure Gage With a Wide Choice of 81 Models and 27 Options To Choose From.Using Dwyer’s Simple, frictionless Magnehelic® Gage movement, it quickly indicates air or noncorrosive gas pressures–either positive, negative vacuum or differential. The design resists shock, vibration, over-pressures and is weatherproof to IP67.Select the -HA High Accuracy Magnehelic® Gage option for an accuracy within 1% of full scale,located below in the Product Configurator.Also included with the–HA option at no extra cost are a mirrored scale overlay and a 6 point calibration certificate.

NIST CALIBRATION available in Product Configurator.

Note: May be used with Hydrogen. Order a Buna-N diaphragm. Pressures must be less than 35 psi.

Please see Series AT-2000 for ATEX approved.

California Residents:Click Here for Proposition 65 WARNING.


PRODUCT APPLICATIONS

  • Filter Monitoring
  • Air Velocity with Dwyer Pitot Tube
  • Blower Vacuum Monitoring
  • Fan Pressure Indication
  • Duct, Room or Building Pressures
  • Clean Room Positive Pressure Indication
Model Description
2000-1.5KPA MAGNEHELIC Differential Pressure Gage,Range 0-1.5 kPa, minor divisions .05.
2000-10KPA MAGNEHELIC Differential Pressure Gage,Range 0-10 kPa, minor divisions .20.
2000-15KPA MAGNEHELIC Differential Pressure Gage,Range 0-15 kPa, minor divisions .50.
2000-1KPA MAGNEHELIC Differential Pressure Gage,Range 0-1 kPa, minor divisions .02.
2000-20KPA MAGNEHELIC Differential Pressure Gage,Range 0-20 kPa, minor divisions .50.
2000-25KPA MAGNEHELIC Differential Pressure Gage,Range 0-25 kPa, minor divisions .50.
2000-2KPA MAGNEHELIC Differential Pressure Gage,Range 0-2 kPa, minor divisions .05.
2000-30KPA MAGNEHELIC Differential Pressure Gage,Range 0-30 kPa, minor divisions 1.0.
2000-3KPA MAGNEHELIC Differential Pressure Gage,Range 0-3 kPa, minor divisions .10.
2000-4KPA MAGNEHELIC Differential Pressure Gage,Range 0-4 kPa, minor divisions .10.
2000-5KPA MAGNEHELIC Differential Pressure Gage,Range 0-5 kPa, minor divisions .10.
2000-8KPA MAGNEHELIC Differential Pressure Gage,Range 0-8 kPa, minor divisions .20.
2300-1KPA MAGNEHELIC Differential Pressure Gage,Range 0.5-0-0.5 kPa,minor divisions .02.
2300-3KPA MAGNEHELIC Differential Pressure Gage,Range 1.5-0-1.5 kPa,minor divisions .10.

 

Additional Information:

www.envirotechindia.info

Magnehelic / Gauge Near Lodha Industrial Park Oragadam Chennai

www.envirotechindustrialproducts.net

Magnehelic / Gauge Near Lodha Industrial Park Oragadam Chennai

 

Series 2000 DWYER Magnehelic Differential Pressure Gauges are Widely Utilized For Measuring Pressure of Fan And Blowing Machine,Resistance of Filter,Wind Speed, Furnace Pressure,Differential Pressure Of Pore Plate,The Pressure of drum water level, Liquid Amplifier And Hydraulic Pressure System.Meantime,They Are Used To Control The Automatic Valve And Specific Value Of Air-Producer Gas In Combustion And They Are Used To Test Blood Pressure And Respiratory Pressure In Medical Health Care Equipment.There Are More Than 81 Models To Suit Your Needs Precisely.The Key Components Adopt Import Materi

SPECIFICATION

  • Ambient Temperature – -21 ~140 -6 ~60
  • Rated Pressure -20 inHg~30 inHg (-68~103KPa)
  • Overpressure – Protective rubber stopper will be blown out if rated pressure is up to about 50.8 inHg (172KPa)
  • Process Connections – 1/8″ Female NPT Duplicate High And Low Pressure Taps – One Pair Side And One Pair Back
  • Housing – Die cast aluminum case and bezel, with acrylic cover,Exterior finish is coated gray to withstand 168 Hour Salt Spray Corrosion Test
  • Accuracy – ±2% of full span at 70 (21 (±3% on -0, and ±4% on -00)
  • Range -20 inHg~38 inHg (-68KPa~130KPa)(Special Specification also can be ordered.

FEATURES

  • OEM/ODM
  • There Is No Need To Fill Liquid To Gauge.
  • The Gauge Can Measure Positive Pressure,Negative Pressure And Differential Pressure.
  • It Will Be Easy To Install And Measure In Different Ways Because Of Two Groups Of Ports Which Can Measure Positive And Negative Pressure.
  • To Eliminate The Friction From The Movement Of Gear Wheel By The Mechanism Of Magnetic Magnet Feed.
  • Exact And Stable Fixed Position Of Needle.
  • The Gauge Has Great Antiknock Characteristics.
  • There Are 81 Types Of Ranges.
  • Minimum is 0-60 Pa And Maximum is 0-21-KPa


PRODUCT APPLICATIONS

  • Filter Monitoring
  • Air Velocity With Pitot Tube
  • Blower Vacuum Monitoring
  • Fan Pressure Indication
  • Duct,Room or Building Pressures
  • Clean Room Positive Pressure Indication

MODELS & ORDERING

DWYER By  Model Number Popularity

 

  • FILTER BY
  • Range – Inches of Water 

 

Model Description
2000-0 MAGNEHELIC® DIFFERENTIAL PRESSURE,Range 0-0.50″ w.c., minor divisions .01, calibrated for vertical scale position.
2000-00 MAGNEHELIC® DIFFERENTIAL PRESSURE,Range 0-0.25″ w.c.,minor divisions .005, calibrated for vertical scale position.
2001 MAGNEHELIC® DIFFERENTIAL PRESSURE,Range 0-1.0″ w.c.,minor divisions .02.
2002 MAGNEHELIC® DIFFERENTIAL PRESSURE,Range 0-2.0″ w.c.,minor divisions .05.
2003 MAGNEHELIC® DIFFERENTIAL PRESSURE,Range 0-3.0″ w.c.,minor divisions .10.
2004 MAGNEHELIC® DIFFERENTIAL PRESSURE,Range 0-4.0″ w.c.,minor divisions .10.
2005 MAGNEHELIC® DIFFERENTIAL PRESSURE,Range 0-5.0″ w.c.,minor divisions .10.
2006 MAGNEHELIC® DIFFERENTIAL PRESSURE,Range 0-6.0″ w.c., minor divisions .20.

Additional Information:

  • Item Code: Magnehelic / Gauge Near Lodha Industrial Park Oragadam Chennai
  • WhatsApp No.9871034100,9868958924,9650264867,9716640145,8368866030,8368801023
  • www.envirotechindustrialproducts.in
  • www.envirotechindustrialproduct.com
  • www.envirotechindustrialproducts.com
  • www.envirotechindustrialproducts.net
  • www.envirotechindustrialproducts.co.in
  • www.envirotechindustrialproduct.co.in
  • www.envirotechindustrialproduct.in

www.envirotechindustrialproducts.net

DWYER / USA MAGNEHELIC Gauge NEAR Dhwani Industrial Park Rajkot


www.envirotechindustrialproducts.net
DWYER / USA MAGNEHELIC Gauge NEAR Dhwani Industrial Park Rajkot

SERIES 2000 MAGNEHELIC® DIFFERENTIAL PRESSURE GAGES Indicate Positive, Negative or Differential, Accurate within 1%

  • No Power Required
  • Low Cost
  • Used in Isolation/ Hospital Environments and Temporary Units (No Power Required)

Select the Series 2000 Magnehelic® Gage for a Versatile Low Differential Pressure Gage With a Wide Choice Of 81 Models And 27 Options To Choose From. Using Dwyer’s simple, frictionless Magnehelic® Gage movement, it quickly indicates air or noncorrosive gas pressures–either positive, negative (vacuum) or differential. The design resists shock, vibration, over-pressures and is weatherproof to IP67. Select the -HA High Accuracy Magnehelic® Gage option for an accuracy within 1% of full scale, located below in the Product Configurator. Also included with the –HA option at no extra cost are a mirrored scale overlay and a 6 point calibration certificate.

NIST CALIBRATION available in Product Configurator.

Note: May be used with Hydrogen. Order a Buna-N diaphragm. Pressures must be less than 35 psi.

Please see Series AT-2000 for ATEX approved.

California Residents:  Click Here for Proposition 65 WARNING.


PRODUCT APPLICATIONS

  • Filter Monitoring
  • Air Velocity with Dwyer Pitot Tube
  • Blower Vacuum Monitoring
  • Fan Pressure Indication
  • Duct, Room or Building Pressures
  • Clean Room Positive Pressure Indication

 

Model Description
2000-1.5KPA Magnehelic Differential Pressure Gage, Range 0-1.5 kPa, minor divisions .05.
2000-10KPA Magnehelic Differential Pressure Gage, Range 0-10 kPa, minor divisions .20.
2000-15KPA Magnehelic Differential Pressure Gage, Range 0-15 kPa, minor divisions .50.
2000-1KPA Magnehelic Differential Pressure Gage, Range 0-1 kPa, minor divisions .02.
2000-20KPA Magnehelic Differential Pressure Gage, Range 0-20 kPa, minor divisions .50.
2000-25KPA Magnehelic Differential Pressure Gage, Range 0-25 kPa, minor divisions .50.
2000-2KPA Magnehelic Differential Pressure Gage, Range 0-2 kPa, minor divisions .05.
2000-30KPA Magnehelic Differential Pressure Gage, Range 0-30 kPa, minor divisions 1.0.
2000-3KPA Magnehelic Differential Pressure Gage, Range 0-3 kPa, minor divisions .10.
2000-4KPA Magnehelic Differential Pressure Gage, Range 0-4 kPa, minor divisions .10.
2000-5KPA Magnehelic Differential Pressure Gage, Range 0-5 kPa, minor divisions .10.
2000-8KPA Magnehelic Differential Pressure Gage, Range 0-8 kPa, minor divisions .20.
2300-1KPA Magnehelic Differential Pressure Gage, Range 0.5-0-0.5 kPa, minor divisions .02.
2300-3KPA Magnehelic Differential Pressure Gage, Range 1.5-0-1.5 kPa, minor divisions .10.

 

Additional Information:

  • Item Code: DWYER : USA MAGNEHELIC Gauge NEAR Dhwani Industrial Park Rajkot
  • WhatsApp No.9871034100,9868958924,9650264867,9716640145,8368866030,8368801023
  • www.envirotechindustrialproducts.co.in
  • www.envirotechindustrialproduct.co.in
  • www.envirotechindustrialproduct.in
  • www.envirotechindustrialproducts.in
  • www.envirotechindustrialproduct.com
  • www.envirotechindustrialproducts.com
  • www.envirotechindustrialproducts.net

www.envirotechindustrialproducts.net

Dwyer Magnehelic Gage In Pithampur Madhya Pradesh

www.envirotechindustrialproducts.in

Dwyer Magnehelic Gage In Pithampur Madhya Pradesh

We are the foremost manufacturer and supplier in the industry by offering Magnehelic Differential Pressure Gauge. This pressure gauge is precisely designed by using best quality materials in compliance with current industry standards with the help of modern equipment. This shock proof pressure gauge is extensively used for the measurement of different gas pressures. We are offering this Magnehelic Differential Pressure Gauge to our broad base of client at a feasible price.

Features:

  • Accurate result
  • Light weight
  • Longer functional life

PRODUCT APPLICATIONS

  • Filter Monitoring
  • Air Velocity with Dwyer Pitot Tube
  • Blower Vacuum Monitoring
  • Fan Pressure Indication
  • Duct,Room or Building Pressures
  • Clean Room Positive Pressure Indication

Sort by  Model Number Popularity

Model Description
2000-0 Differential pressure gage, range 0-0.50″ w.c., minor divisions .01, calibrated for vertical scale position.
2000-0-SP Differential pressure gage, range 0-0.50″ w.c., with set point indicator.
2000-00 Differential pressure gage, range 0-0.25″ w.c., minor divisions .005, calibrated for vertical scale position.
2000-00AV Differential pressure gage, range 0-0.25″ w.c., velocity 300-2000 FPM, calibrated for vertical scale position.
2000-00N Differential pressure gage, range .05-0-.2″ w.c., minor divisions .005, calibrated for vertical scale position.
2000-0AV Differential pressure gage, range 0-0.50″ w.c., velocity 500-2800 FPM, calibrated for vertical scale position.
2000-0D Differential pressure gage, range 0-0.5″ w.c. & 0-125 Pa.
2000-1.5KPA Differential pressure gage, range 0-1.5 kPa, minor divisions .05.
2000-100CM Differential pressure gage, range 0-100 cm w.c., minor divisions 2.0.
2000-100MM Differential pressure gage, range 0-100 mm w.c., minor divisions 2.0.
2000-100PA Differential pressure gage, range 0-100 Pa, minor divisions 2.0, calibrated for vertical scale position.
2000-10KPA Differential pressure gage, range 0-10 kPa, minor divisions .20.
2000-10MM Differential pressure gage, range 0-10 mm w.c., minor divisions .20, calibrated for vertical scale position.
2000-125PA Differential pressure gage, range 0-125 Pa, minor divisions 5.0, calibrated for vertical scale position.
2000-150CM Differential pressure gage, range 0-150 cm w.c., minor divisions 5.0.
2000-150MM Differential pressure gage, range 0-150 mm w.c.
2000-15CM Differential pressure gage, range 0-15 cm w.c., minor divisions .50.
2000-15KPA Differential pressure gage, range 0-15 kPa, minor divisions .50.
2000-15MM Differential pressure gage, range 0-15 mm w.c.
2000-1KPA Differential pressure gage, range 0-1 kPa, minor divisions .02.
2000-200CM Differential pressure gage, range 0-200 cm w.c., minor divisions 5.0.
2000-200MM Differential pressure gage, range 0-200 mm w.c.
2000-20CM Differential pressure gage, range 0-20 cm w.c., minor divisions .50.
2000-20KPA Differential pressure gage, range 0-20 kPa, minor divisions .50.
2000-250CM Differential pressure gage, range 0-250 cm w.c., minor divisions 5.0.
2000-250MM Differential pressure gage, range 0-250 mm w.c.
2000-250PA Differential pressure gage, range 0-250 Pa, minor divisions 5.0.
2000-25CM Differential pressure gage, range 0-25 cm w.c., minor divisions .50.
2000-25KPA Differential pressure gage, range 0-25 kPa, minor divisions .50.
2000-25MM Differential pressure gage, range 0-25 mm w.c., minor divisions .50.
2000-2KPA Differential pressure gage, range 0-2 kPa, minor divisions .05.
2000-300CM Differential pressure gage, range 0-300 cm w.c., minor divisions 10.0.
2000-300MM Differential pressure gage, range 0-300 mm w.c.
2000-300PA Differential pressure gage, range 0-300 Pa, minor divisions 10.0.
2000-30KPA Differential pressure gage, range 0-30 kPa, minor divisions 1.0.
2000-30PA Differential pressure gage, range 0-30 Pa, minor divisions 1.0, calibrated for vertical scale position.
2000-3KPA Differential pressure gage, range 0-3 kPa, minor divisions .10.
2000-4KPA Differential pressure gage, range 0-4 kPa, minor divisions .10.
2000-500PA Differential pressure gage, range 0-500 Pa, minor divisions 10.0.
2000-50CM Differential pressure gage, range 0-50 cm w.c., minor divisions 1.0.
2000-50MM Differential pressure gage, range 0-50 mm w.c., minor divisions 1.0.
2000-5KPA Differential pressure gage, range 0-5 kPa, minor divisions .10.
2000-60PA Differential pressure gage, range 0-60 Pa, minor divisions 1.0, calibrated for vertical scale position.
2000-6MM Differential pressure gage, range 0-6 mm w.c., minor divisions .20, calibrated for vertical scale position.
2000-750PA Differential pressure gage, range 0-750 Pa, minor divisions 25.0.
2000-80CM Differential pressure gage, range 0-80 cm w.c., minor divisions 2.0.
2000-80MM Differential pressure gage, range 0-80 mm w.c., minor divisions 2.0.
2000-8KPA Differential pressure gage, range 0-8 kPa, minor divisions .20.
2001 Differential pressure gage, range 0-1.0″ w.c., minor divisions .02.
2001-SP Differential pressure gage, range 0-1″ w.c., with set point indicator.
2001AV Differential pressure gage, range 0-1.0″ w.c., velocity 500-4000 FPM.
2001D Differential pressure gage, range 0-1.0″ w.c. & 0-250 Pa.
2002 Differential pressure gage, range 0-2.0″ w.c., minor divisions .05.
2002-SP Differential pressure gage, range 0-2″ w.c., with set point indicator.
2002AV Differential pressure gage, range 0-2.0″ w.c., velocity 1000-5600 FPM.
2002D Differential pressure gage, range 0-2.0″ w.c. & 0-500 Pa.
2003 Differential pressure gage, range 0-3.0″ w.c., minor divisions .10.
2003D Differential pressure gage, range 0-3.0″ w.c. & 0-750 Pa.
2004 Differential pressure gage, range 0-4.0″ w.c., minor divisions .10.
2004D Differential pressure gage, range 0-4.0″ w.c. & 0-1.0 kPa.
2005 Differential pressure gage, range 0-5.0″ w.c., minor divisions .10.
2005-SP Differential pressure gage, range 0-5″ w.c., with set point indicator.
2006 Differential pressure gage, range 0-6.0″ w.c., minor divisions .20.
2006D Differential pressure gage, range 0-6.0″ w.c. & 0-1.5 kPa.
2008 Differential pressure gage, range 0-8.0″ w.c., minor divisions .20.
2008D Differential pressure gage, range 0-8.0″ w.c. & 0-2.0 kPa.
2010 Differential pressure gage, range 0-10″ w.c., minor divisions .20.
2010-SP Differential pressure gage, range 0-10″ w.c., with set point indicator.
2010AV Differential pressure gage, range 0-10″ w.c., velocity 2000-12500 FPM.
2010D Differential pressure gage, range 0-10″ w.c. & 0-2.5 kPa.
2015 Differential pressure gage, range 0-15″ w.c., minor divisions .50.
2015D Differential pressure gage, range 0-15″ w.c. & 0-3.7 kPa.
2020 Differential pressure gage, range 0-20″ w.c., minor divisions .50.
2025 Differential pressure gage, range 0-25″ w.c., minor divisions .50.
2030 Differential pressure gage, range 0-30″ w.c., minor divisions 1.0.
2040 Differential pressure gage, range 0-40″ w.c., minor divisions 1.0.
2050 Differential pressure gage, range 0-50″ w.c., minor divisions 1.0.
2060 Differential pressure gage, range 0-60″ w.c., minor divisions 2.0.
2080 Differential pressure gage, range 0-80″ w.c., minor divisions 2.0.
2100 Differential pressure gage, range 0-100″ w.c., minor divisions 2.0.
2150 Differential pressure gage, range 0-150″ w.c., minor divisions 5.0.
2201 Differential pressure gage, range 0-1 psi, minor divisions .02.
2202 Differential pressure gage, range 0-2 psi, minor divisions .05.
2203 Differential pressure gage, range 0-3 psi, minor divisions .10.
2204 Differential pressure gage, range 0-4 psi, minor divisions .10.
2205 Differential pressure gage, range 0-5 psi, minor divisions .10.
2210 Differential pressure gage, range 0-10 psi, minor divisions .20, MP option standard.
2215 Differential pressure gage, range 0-15 psi, minor divisions .50, MP option standard.
2220 Differential pressure gage, range 0-20 psi, minor divisions .50, MP option standard.
2230 Differential pressure gage, range 0-30 psi, minor divisions 1.0, HP option standard.
2300-0 Differential pressure gage, range 0.25-0-0.25″ w.c., minor divisions .01, calibrated for vertical scale position.
2300-100PA Differential pressure gage, range 50-0-50 Pa, minor divisions 2.0, calibrated for vertical scale position.
2300-10CM Differential pressure gage, range 5-0-5 cm w.c., minor divisions .20.
2300-120PA Differential pressure gage, range 60-0-60 Pa, minor divisions 2.0.
2300-1KPA Differential pressure gage, range 0.5-0-0.5 kPa, minor divisions .02.
2300-20MM Differential pressure gage, range 10-0-10 mm w.c., minor divisions .50, calibrated for vertical scale position.
2300-250PA Differential pressure gage, range 125-0-125 Pa, minor divisions 5.0.
2300-30CM Differential pressure gage, range 15-0-15 cm w.c., minor divisions 1.0.
2300-3KPA Differential pressure gage, range 1.5-0-1.5 kPa, minor divisions .10.
2300-4CM Differential pressure gage, range 2-0-2 cm w.c., minor divisions .10.
2300-500PA Differential pressure gage, range 250-0-250 Pa, minor divisions 10.0.
2300-60PA Differential pressure gage, range 30-0-30 Pa, minor divisions 1.0, calibrated for vertical scale position.
2301 Differential pressure gage, range 0.5-0-0.5″ w.c., minor divisions .02.
2302 Differential pressure gage, range 1-0-1″ w.c., minor divisions .05.
2304 Differential pressure gage, range 2-0-2″ w.c., minor divisions .10.
2310 Differential pressure gage, range 5-0-5″ w.c., minor divisions .20.
2320 Differential pressure gage, range 10-0-10″ w.c., minor divisions .50.
2330 Differential pressure gage, range 15-0-15″ w.c., minor divisions 1.0.

Additional Information:

  • Item Code: Dwyer Magnehelic Gage In Pithampur Madhya Pradesh
  • www.envirotechindustrialproducts.co.in
  • www.envirotechindustrialproduct.co.in
  • www.envirotechindustrialproduct.in
  • www.envirotechindustrialproducts.in
  • www.envirotechindustrialproduct.com
  • www.envirotechindustrialproducts.com

www.envirotechindustrialproducts.in

Dwyer Omega EDPS-05-1-N Adjustable Differential Pressure Switch

www.envirotechindia.info

Dwyer Omega EDPS-05-1-N Adjustable Differential Pressure Switch

Series ADPS/EDPS Differential Pressure Switch With Dual Scale Field Adjustable Set Point Knob

The Series ADPS/EDPS Adjustable Differential Pressure Switch is designed for pressure, vacuum, and differential pressures. The dual scaled adjustment knob in inches water column and pascals allows changes to the switching pressure to be made without a pressure gage. The ADPS/EDPS is available with settings from 0.08 in w.c. (20 Pa) up to 20 in w.c. (5000 Pa). The silicone diaphragm and PA 6.6 body make the series ADPS ideal for use with air and other noncombustible gases. Series EDPS models meet UL508 and are constructed of plenum rated plastics. The compact size, adjustment knob and low cost make the ADPS/EDPS the perfect choice for HVAC applications.

Please see Series AT-ADPS for ATEX approved.

Product Applications

  • Monitoring air filters and ventilators.
  • Monitoring industrial cooling-air circuits.
  • Overheating protection for fan heaters.
  • Monitoring flows in ventilation ducts.
  • Controlling air and fire-protection dampers.
  • Frost protection for heat exchanges.

Models & Ordering

Model Description
ADPS-03-1-N Adjustable differential pressure switch, set point range 0.20 to 2.00″ w.c., 1/2″ NPT connection.
ADPS-03-2-N Adjustable differential pressure switch, set point range 0.20 to 2.00″ w.c., M20 connection.
ADPS-03-2-N-C Adjustable differential pressure switch, set point range 0.20 to 2.00″ w.c., M20 connection, with two static tips and 7 ft (2.1 m) of PVC tubing.
ADPS-04-1-N Adjustable differential pressure switch, set point range 0.12 to 1.60″ w.c., 1/2″ NPT connection.
ADPS-04-2-N Adjustable differential pressure switch, set point range 0.12 to 1.60″ w.c., M20 connection.
ADPS-04-2-N-C Adjustable differential pressure switch, set point range 0.12 to 1.60″ w.c., M20 connection, with two static tips and 7 ft (2.1 m) of PVC tubing.
ADPS-05-1-N Adjustable differential pressure switch, set point range 0.80 to 4.00″ w.c., 1/2″ NPT connection.
ADPS-05-2-N Adjustable differential pressure switch, set point range 0.80 to 4.00″ w.c., M20 connection.
ADPS-05-2-N-C Adjustable differential pressure switch, set point range 0.80 to 4.00″ w.c., M20 connection, with two static tips and 7 ft (2.1 m) of PVC tubing.
ADPS-06-1-N Adjustable differential pressure switch, set point range 2.00 to 10.00″ w.c., 1/2″ NPT connection.
ADPS-06-2-N Adjustable differential pressure switch, set point range 2.00 to 10.00″ w.c., M20 connection.
ADPS-06-2-N-C Adjustable differential pressure switch, set point range 2.00 to 10.00″ w.c., M20 connection, with two static tips and 7 ft (2.1 m) of PVC tubing.
ADPS-07-1-N Adjustable differential pressure switch, set point range 4.00 to 20.00″ w.c., 1/2″ NPT connection.
ADPS-07-2-N Adjustable differential pressure switch, set point range 4.00 to 20.00″ w.c., M20 connection.
ADPS-07-2-N-C Adjustable differential pressure switch, set point range 4.00 to 20.00″ w.c., M20 connection, with two static tips and 7 ft (2.1 m) of PVC tubing.
ADPS-08-1-N Adjustable differential pressure switch, set point range 0.08 to 1.20″ w.c., 1/2″ NPT connection.
ADPS-08-2-N Adjustable differential pressure switch, set point range 0.08 to 1.20″ w.c., M20 connection.
ADPS-08-2-N-C Adjustable differential pressure switch, set point range 0.08 to 1.20″ w.c., M20 connection, with two static tips and 7 ft (2.1 m) of PVC tubing.
EDPS-03-1-N Adjustable differential pressure switch, range .20-2.00″ w.c., with 1/2″ NPT connection.
EDPS-03-2-N Adjustable differential pressure switch, range .20-2.00″ w.c., with M20 connection.
EDPS-04-1-N Adjustable differential pressure switch, range .12-1.60″ w.c., with 1/2″ NPT connection.
EDPS-04-2-N Adjustable differential pressure switch, range .12-1.60″ w.c., with M20 connection.
EDPS-05-1-N Adjustable differential pressure switch, range .80-4.00″ w.c., with 1/2″ NPT connection.
EDPS-05-2-N Adjustable differential pressure switch, range .80-4.00″ w.c., with M20 connection.
EDPS-06-1-N Adjustable differential pressure switch, range 2.00-10.00″ w.c., with 1/2″ NPT connection.
EDPS-06-2-N Adjustable differential pressure switch, range 2.00-10.00″ w.c., with M20 connection.
EDPS-07-1-N Adjustable differential pressure switch, range 4.00-20.00″ w.c., with 1/2″ NPT connection.
EDPS-08-1-N Adjustable differential pressure switch, range .08-1.20″ w.c., with 1/2″ NPT connection.
EDPS-08-2-N Adjustable differential pressure switch, range .08-1.20″ w.c., with M20 connection.

Specifications

  • Service:Air and non-combustible, compatible gases.
  • Wetted Materials:
  • ADPS: Diaphragm material: Silicone; Housing Material: POM; Switch body: PA 6.6; Cover: Polystyrene;
  • EDPS: Diaphragm material: Silicone; Housing material: Switch body: PA 6.6; Cover: Polystyrene; Materials UL 94 V-0 rated.
  • Temperature Limits:Process and ambient temperature from -4 to 185°F (-20 to 85°C).
  • Storage:-40 to 185°F (-40 to 85°C).
  • Pressure Limits:Max. Operating Pressure: 40″ w.c. (10 kPa) for all pressure ranges.
  • Switch Type:Single-pole double-throw (SPDT).
  • Electrical Rating:Max. 1.5 A res./0.4 A ind./250 VAC, 50/60 Hz; Max. switching rate: 6 cycles/min.
  • Electrical Connections:Push-on screw terminals. M20x1.5 with cable strain relief or optional 1/2″ NPT connection.
  • Process Connections:5/16″ (7.94 mm) outside diameter tubing, 1/4″ (6.0 mm) inside diameter tubing.
  • Enclosure Rating:NEMA 3 (IP54).
  • Mounting Orientation:Vertically, with pressure connections pointing downwards.
  • Mechanical Working Life:Over 106 switching operations.
  • Weight:4.4 oz (125 g).Agency
  • Approvals:CE, ETL approved to UL508 and CSA C22.2#14 (EDPS only).

Features

  • Adjustment knob changes switching pressure easily with a pressure gage reducing components for application
  • Low cost device makes it an excellent solution in BAS and HVAC applications requiring duct control and monitoring
  • Relay contact allows simple integration with DDC or building systems

Product Literature

Manuals

Catalog Pages

Product Data Sheet

Additional Information:

  • Dwyer Omega EDPS-05-1-N Adjustable Differential Pressure Switch
  • www.envirotechdelhi.com
  • www.envirotechindia.co.in
  • www.envirotechdelhi.in
    www.envirotechdelhi.net
  • www.envirotechindia.info
  • www.envirotechdelhi.info
  • www.envirotechindia.net
  • www.envirotechdelhi.co.in

www.envirotechindia.info

 

Dwyer Differential Pressure Switch Wholesaler

Dwyer BDPA-07-2-N Adjustable Differential Pressure Switch

 
 
Media TypeGas
Weight6.1 oz (173 g)
Model NumberBDPA-07-2-N
Electrical Rating1.0 A @ 30 VDC/VAC
BrandDWYER
Temperature Limits32 to 122 DegreeF (0 to 50 DegreeC)
Pressure Limits40″ w.c. (10 kPa)
Switch TypeSPDT
Enclosure RatingIP21


The Series BDPA Adjustable Differential Pressure Alarm with built-in audible and visual set point indication is designed for overpressure, vacuum, and differential pressure applications. The scaled adjustment knob allows changes to the switching pressure to be made without a pressure gage. The silicone diaphragm and PA 6.6 body make the Series BDPA perfect for use with air and other noncombustible gases.

The Series BDPA Adjustable Differential Pressure Alarms offer a versatile range of configurations allowing utilization of their many features. The BDPA can be powered by battery or 24 VDC/VAC line power. If connecting line power, the battery can act as back-up power in case of power outage. When set point threshold is reached, a local loud audible buzzer and bright LED will indicate periodically notifying of set point activation. An SPDT contact may also be wired to send a signal remotely to a DDC or building management system. A snooze button located through an opening in the cover can be pressed by the user to manually disengage the audible and visual indication until a maintenance operation is performed. If the instrument is mounted where it is difficult to access, a remote contact may be connected allowing the user to deactivate the buzzer and LED at the remote contact location.

The Series BDPA Differential Pressure Alarm’s great functional versatility makes it perfect for filter, fan, and ventilation applications or any retrofit job where installing electrical wiring proves cost-prohibitive.

Note: For a 1/2″ npt connection, use the 1/2″ conduit fitting adapter (A-483).

Approvals

  • CE Approval
  • Reduction of Hazardous Substance (RoHS)


Specification

ServiceAir and noncombustible, compatible gases
Wetted MaterialsDiaphragm: Silicone; Housing: Switch Body: PA 6.6 and POM; Cover: Polystyrene
Temperature Limits32 to 122°F (0 to 50°C)
Pressure Limits40″ w.c. (10 kPa)
Electrical Rating1.0 A @ 30 VDC/VAC
Switch TypeSPDT
Alarm Indicationrm.Red LED and audible alarm
Alarm LevelApproximately 90 db at 4″ (10 cm)
Alarm AcknowledgeButton press
Power Requirements16 to 30 VDC, 18 to 30 VAC or 3.6 V LS14250 lithium metal battery, installed functional, user replaceable. Battery acts as back-up if power is lost
Battery LifeApproximately 1.5 years with 3.6 V/1.2 Ah
Repeatability±15% FS
Electrical ConnectionsScrew terminals. M20x1.5 with cable strain relief or optional 1/2″ NPT connection
Process Connections5/16″ (7.94 mm) outside diameter tubing, 1/4″ (6.0 mm) inside diameter tubing
Mounting OrientationVertically, with pressure connections pointing downwards
Enclosure RatingIP21
Weight6.1 oz (173 g)
Agency ApprovalsCE, RoHS

Dwyer BDPA-06-2-N Adjustable Differential Pressure Switch

 
 
Media TypeGas
Weight6.1 oz (173 g)
Model NumberBDPA-06-2-N
Electrical Rating1.0 A @ 30 VDC/VAC
BrandDWYER
Temperature Limits32 to 122 DegreeF (0 to 50 DegreeC)
Pressure Limits40″ w.c. (10 kPa)
Switch TypeSPDT
Enclosure RatingIP21


The Series BDPA Adjustable Differential Pressure Alarm with built-in audible and visual set point indication is designed for overpressure, vacuum, and differential pressure applications. The scaled adjustment knob allows changes to the switching pressure to be made without a pressure gage. The silicone diaphragm and PA 6.6 body make the Series BDPA perfect for use with air and other noncombustible gases.

The Series BDPA Adjustable Differential Pressure Alarms offer a versatile range of configurations allowing utilization of their many features. The BDPA can be powered by battery or 24 VDC/VAC line power. If connecting line power, the battery can act as back-up power in case of power outage. When set point threshold is reached, a local loud audible buzzer and bright LED will indicate periodically notifying of set point activation. An SPDT contact may also be wired to send a signal remotely to a DDC or building management system. A snooze button located through an opening in the cover can be pressed by the user to manually disengage the audible and visual indication until a maintenance operation is performed. If the instrument is mounted where it is difficult to access, a remote contact may be connected allowing the user to deactivate the buzzer and LED at the remote contact location.

The Series BDPA Differential Pressure Alarm’s great functional versatility makes it perfect for filter, fan, and ventilation applications or any retrofit job where installing electrical wiring proves cost-prohibitive.

Note: For a 1/2″ npt connection, use the 1/2″ conduit fitting adapter (A-483).

Approvals

  • CE Approval
  • Reduction of Hazardous Substance (RoHS)


Specification

ServiceAir and noncombustible, compatible gases
Wetted MaterialsDiaphragm: Silicone; Housing: Switch Body: PA 6.6 and POM; Cover: Polystyrene
Temperature Limits32 to 122°F (0 to 50°C)
Pressure Limits40″ w.c. (10 kPa)
Electrical Rating1.0 A @ 30 VDC/VAC
Switch TypeSPDT
Alarm Indicationrm.Red LED and audible alarm
Alarm LevelApproximately 90 db at 4″ (10 cm)
Alarm AcknowledgeButton press
Power Requirements16 to 30 VDC, 18 to 30 VAC or 3.6 V LS14250 lithium metal battery, installed functional, user replaceable. Battery acts as back-up if power is lost
Battery LifeApproximately 1.5 years with 3.6 V/1.2 Ah
Repeatability±15% FS
Electrical ConnectionsScrew terminals. M20x1.5 with cable strain relief or optional 1/2″ NPT connection
Process Connections5/16″ (7.94 mm) outside diameter tubing, 1/4″ (6.0 mm) inside diameter tubing
Mounting OrientationVertically, with pressure connections pointing downwards
Enclosure RatingIP21
Weight6.1 oz (173 g)
Agency ApprovalsCE, RoHS

Dwyer BDPA-05-2-N Adjustable Differential Pressure Switch

 
 
Weight6.1 oz (173 g)
Model NumberBDPA-05-2-N
Electrical Rating1.0 A @ 30 VDC/VAC
BrandDWYER
Temperature Limits32 to 122 DegreeF (0 to 50 DegreeC)
Pressure Limits40″ w.c. (10 kPa)
Switch TypeSPDT
Enclosure RatingIP 21


The Series BDPA Adjustable Differential Pressure Alarm with built-in audible and visual set point indication is designed for overpressure, vacuum, and differential pressure applications. The scaled adjustment knob allows changes to the switching pressure to be made without a pressure gage. The silicone diaphragm and PA 6.6 body make the Series BDPA perfect for use with air and other noncombustible gases.

The Series BDPA Adjustable Differential Pressure Alarms offer a versatile range of configurations allowing utilization of their many features. The BDPA can be powered by battery or 24 VDC/VAC line power. If connecting line power, the battery can act as back-up power in case of power outage. When set point threshold is reached, a local loud audible buzzer and bright LED will indicate periodically notifying of set point activation. An SPDT contact may also be wired to send a signal remotely to a DDC or building management system. A snooze button located through an opening in the cover can be pressed by the user to manually disengage the audible and visual indication until a maintenance operation is performed. If the instrument is mounted where it is difficult to access, a remote contact may be connected allowing the user to deactivate the buzzer and LED at the remote contact location.

The Series BDPA Differential Pressure Alarm’s great functional versatility makes it perfect for filter, fan, and ventilation applications or any retrofit job where installing electrical wiring proves cost-prohibitive.

Note: For a 1/2″ npt connection, use the 1/2″ conduit fitting adapter (A-483).

Approvals:

  • CE Approval
  • Reduction of Hazardous Substance (RoHS)

 

Specification:

ServiceAir and noncombustible, compatible gases
Wetted MaterialsDiaphragm: Silicone; Housing: Switch Body: PA 6.6 and POM; Cover: Polystyrene
Temperature Limits32 to 122°F (0 to 50°C)
Pressure Limits40″ w.c. (10 kPa)
Electrical Rating1.0 A @ 30 VDC/VAC
Switch TypeSPDT
Alarm Indicationrm.Red LED and audible alarm
Alarm LevelApproximately 90 db at 4″ (10 cm)
Alarm AcknowledgeButton press
Power Requirements16 to 30 VDC, 18 to 30 VAC or 3.6 V LS14250 lithium metal battery, installed functional, user replaceable. Battery acts as back-up if power is lost
Battery LifeApproximately 1.5 years with 3.6 V/1.2 Ah
Repeatability±15% FS
Electrical ConnectionsScrew terminals. M20x1.5 with cable strain relief or optional 1/2″ NPT connection
Process Connections5/16″ (7.94 mm) outside diameter tubing, 1/4″ (6.0 mm) inside diameter tubing
Mounting OrientationVertically, with pressure connections pointing downwards
Enclosure RatingIP21
Weight6.1 oz (173 g)
Agency ApprovalsCE, RoHS

Dwyer BDPA-03-2-N Adjustable Differential Pressure Switch

 
 
Current Rating1.5 A
Weight160 g
Temperature Limits-4 to 185degF
Pressure Limit10 kPa
Process Connection5/16″
Voltage250 VAC


Dwyer BDPA-03-2-N Adjustable Differential Pressure Switch

Series BDPA Adjustable Differential Pressure Alarm .20-2.00″ w.c.

24 Volt or Battery Powered, Built-in Audible and Visual Alarm

The Series BDPA Adjustable Differential Pressure Alarm with built-in audible and visual set point indication is designed for overpressure, vacuum, and differential pressure applications. The scaled adjustment knob allows changes to the switching pressure to be made without a pressure gage. The silicone diaphragm and PA 6.6 body make the Series BDPA perfect for use with air and other noncombustible gases.

The Series BDPA Adjustable Differential Pressure Alarms offer a versatile range of configurations allowing utilization of their many features. The BDPA can be powered by battery or 24 VDC/VAC line power. If connecting line power, the battery can act as back-up power in case of power outage. When set point threshold is reached, a local loud audible buzzer and bright LED will indicate periodically notifying of set point activation. An SPDT contact may also be wired to send a signal remotely to a DDC or building management system. A snooze button located through an opening in the cover can be pressed by the user to manually disengage the audible and visual indication until a maintenance operation is performed. If the instrument is mounted where it is difficult to access, a remote contact may be connected allowing the user to deactivate the buzzer and LED at the remote contact location.

The Series BDPA Differential Pressure Alarm’s great functional versatility makes it perfect for filter, fan, and ventilation applications or any retrofit job where installing electrical wiring proves cost-prohibitive.

Note: For a 1/2″ npt connection, use the 1/2″ conduit fitting adapter (A-483).

Approvals

  • Reduction of Hazardous Substance (RoHS)
  • CE Approval

Specification

ServiceAir and noncombustible, compatible gases
Wetted MaterialsDiaphragm: Silicone; Housing: Switch Body: PA 6.6 and POM; Cover: Polystyrene
Temperature Limits32 to 122°F (0 to 50°C)
Pressure Limits40″ w.c. (10 kPa)
Electrical Rating1.0 A @ 30 VDC/VAC
Switch TypeSPDT
Alarm Indicationrm.Red LED and audible alarm
Alarm LevelApproximately 90 db at 4″ (10 cm)
Alarm AcknowledgeButton press
Power Requirements16 to 30 VDC, 18 to 30 VAC or 3.6 V LS14250 lithium metal battery, installed functional, user replaceable. Battery acts as back-up if power is lost
Battery LifeApproximately 1.5 years with 3.6 V/1.2 Ah
Repeatability±15% FS
Electrical ConnectionsScrew terminals. M20x1.5 with cable strain relief or optional 1/2″ NPT connection
Process Connections5/16″ (7.94 mm) outside diameter tubing, 1/4″ (6.0 mm) inside diameter tubing
Mounting OrientationVertically, with pressure connections pointing downwards
Enclosure RatingIP21
Weight6.1 oz (173 g)
Agency ApprovalsCE, RoHS

Dwyer BDPA-04-2-N Adjustable Differential Pressure Switch

 
 
Current Rating1.5 A
Media TypeGas
Power/Voltage250 VAC
Weight160 g
Model NumberBDPA-04-2-N
BrandDWYER
Temperature Limits-4 to 185degF
Pressure Limit10 kPa
Process Connection5/16″
Frequency50/60 Hz


The Series BDPA Adjustable Differential Pressure Alarm with built-in audible and visual set point indication is designed for overpressure, vacuum, and differential pressure applications. The scaled adjustment knob allows changes to the switching pressure to be made without a pressure gage. The BDPA is available with settings from 0.08″ w.c. (20 Pa) to 20″ w.c. (5000 Pa). The silicone diaphragm and PA 6.6 body make the Series BDPA perfect for use with air and other noncombustible gases.

The Series BDPA Adjustable Differential Pressure Alarms offer a versatile range of configurations allowing utilization of their many features. The BDPA can be powered by battery or 24 VDC/VAC line power. If connecting line power, the battery can act as back-up power in case of power outage. When set point threshold is reached, a local loud audible buzzer and bright LED will indicate periodically notifying of set point activation. An SPDT contact may also be wired to send a signal remotely to a DDC or building management system. A snooze button located through an opening in the cover can be pressed by the user to manually disengage the audible and visual indication until a maintenance operation is performed. If the instrument is mounted where it is difficult to access, a remote contact may be connected allowing the user to deactivate the buzzer and LED at the remote contact location.

The Series BDPA Differential Pressure Alarm’s great functional versatility makes it perfect for filter, fan, and ventilation applications or any retrofit job where installing electrical wiring proves cost-prohibitive.

 

Note: For a 1/2″ npt connection, use the 1/2″ conduit fitting adapter (A-483).


Product Applications:

  • Air filter and ventilator monitoring
  • Industrial cooling circuits
  • Fire-protection damper control
  • Ventilation duct monitoring
  • Fan heater overheating protection
  • Heat exchanger frost protection



Specification:

ServiceAir and noncombustible, compatible gases
Wetted MaterialsDiaphragm: Silicone; Housing: Switch Body: PA 6.6 and POM; Cover: Polystyrene
Temperature Limits32 to 122°F (0 to 50°C)
Pressure Limits40″ w.c. (10 kPa)
Electrical Rating1.0 A @ 30 VDC/VAC
Switch TypeSPDT
Alarm Indicationrm.Red LED and audible alarm
Alarm LevelApproximately 90 db at 4″ (10 cm)
Alarm AcknowledgeButton press
Power Requirements16 to 30 VDC, 18 to 30 VAC or 3.6 V LS14250 lithium metal battery, installed functional, user replaceable. Battery acts as back-up if power is lost
Battery LifeApproximately 1.5 years with 3.6 V/1.2 Ah
Repeatability±15% FS
Electrical ConnectionsScrew terminals. M20x1.5 with cable strain relief or optional 1/2″ NPT connection
Process Connections5/16″ (7.94 mm) outside diameter tubing, 1/4″ (6.0 mm) inside diameter tubing
Mounting OrientationVertically, with pressure connections pointing downwards
Enclosure RatingIP21
Weight6.1 oz (173 g)
Agency ApprovalsCE, RoHS

Dwyer BDPA-08-2-N Adjustable Differential Pressure Switch

 
 
Current Rating1.5 A
Process Temperature-40 to 185degF
Pressure Limit10 kPa
Voltage250 VAC
Frequency50 Hz
Process Connection5/16″


The Series BDPA Adjustable Differential Pressure Alarm with built-in audible and visual set point indication is designed for overpressure, vacuum, and differential pressure applications. The scaled adjustment knob allows changes to the switching pressure to be made without a pressure gage. The BDPA is available with settings from 0.08″ w.c. (20 Pa) to 20″ w.c. (5000 Pa). The silicone diaphragm and PA 6.6 body make the Series BDPA perfect for use with air and other noncombustible gases.

The Series BDPA Adjustable Differential Pressure Alarms offer a versatile range of configurations allowing utilization of their many features. The BDPA can be powered by battery or 24 VDC/VAC line power. If connecting line power, the battery can act as back-up power in case of power outage. When set point threshold is reached, a local loud audible buzzer and bright LED will indicate periodically notifying of set point activation. An SPDT contact may also be wired to send a signal remotely to a DDC or building management system. A snooze button located through an opening in the cover can be pressed by the user to manually disengage the audible and visual indication until a maintenance operation is performed. If the instrument is mounted where it is difficult to access, a remote contact may be connected allowing the user to deactivate the buzzer and LED at the remote contact location.

The Series BDPA Differential Pressure Alarm’s great functional versatility makes it perfect for filter, fan, and ventilation applications or any retrofit job where installing electrical wiring proves cost-prohibitive.

Note: For a 1/2″ npt connection, use the 1/2″ conduit fitting adapter (A-483).

Product Applications

  • Air filter and ventilator monitoring
  • Industrial cooling circuits
  • Fire-protection damper control
  • Ventilation duct monitoring
  • Fan heater overheating protection
  • Heat exchanger frost protection



PRODUCT DESCRIPTIONDwyer Instruments BDPA-08-2-N, Adjustable differential pressure alarm, range .08-1.20 w.c., M20 connection. 
Adjustable differential pressure alarm, range .08-1.20 w.c., M20 connection.
24 Volt or Battery Powered, Built-in Audible and Visual Alarm
Item Specifications

  • Service: Air and noncombustible, compatible gases.
  • Wetted Materials: Diaphragm: Silicone; Housing: Switch Body: PA 6.6 and POM; Cover: Polystyrene.
  • Temperature Limits: 32 to 122°F (0 to 50°C).
  • pressure Limits: 40 w.c. (10 kPa).
  • Electrical Rating: 1.0 A @ 30 VDC/VAC/span>
  • Switch Type: SPDT.
  • Alarm Indicationrm.: Red LED and audible alarm.
  • Alarm Level: Approximately 90db at 4 (10 cm).
  • Alarm Acknowledge: Button preSS.
  • Power Requirements: 16 to 30 VDC, 18 to 30 VACor 3.6 V LS14250 lithium metal battery, installed functional, user replaceable. Battery acts as back-up if power is lost.
  • Battery Life: Approximately 1.5 years with 3.6 V/1.2 Ah.
  • Repeatability: _15% FS.
  • Electrical Connections: Screw terminals. M20x1.5 with cable strain relief or optional 1/2 NPT connection.
  • process Connections: 5/16 (7.94 mm) outside diameter tubing, 1/4 (6.0 mm) inside diameter tubing.
  • Mounting Orientation: Vertically, with pressure connections pointing downwards.
  • Weight: 6.1 oz (173 g).
  • Enclosure Rating: IP21.
  • Agency Approvals: CE, RoHS.

FIND SIMILAR PRODUCTS BY CATEGORY

  • Dwyer Instruments
  • Pressure
  • Differential Pressure
  • Switches

Dwyer Differential Pressure Switch

 
 
Current Rating1.5 A
Model No.ADPS-07-2-N
Media TypeGas
Weight160 g
BrandDWYER
Temperature Limits-4 to 185degF
Pressure Limit10 kPa
Process Connection5/16″
Voltage250 VAC


Our firm offers a high-quality range of Dwyer Differential Pressure Switch.

Features:

  • HVAC Differential Pressure Switch with Dual scale filed adjustable Set Point Knob.
  • The compact size, adjustment knob and low cost makes ADPS/EDPS the perfect choice for HVAC applications.


Applications:

  • Monitoring air filters and ventilators
  • Overheating protection for fan heaters
  • Monitoring industrial cooling air circuits
  • Monitoring flow in duct ventilation
  • Controlling air and fire protection dampers

Dwyer EDPS-07-1-N Adjustable Differential Pressure Switch

 
 
Current Rating1.5 A
Model No.EDPS-07-1-N
Weight160 g
BrandDWYER
Temperature Limits-4 to 185degF
Pressure Limit10 kPa
Process Connection5/16″


The Series EDPS Adjustable Differential Pressure Switch is designed for pressure, vacuum, and differential pressures. The dual scaled adjustment knob in inches water column and pascals allows changes to the switching pressure to be made without a pressure gage. The EDPS is available with settings from 0.08″ w.c. (20 Pa) up to 16″ w.c. (4000 Pa). The silicone diaphragm and PA 6.6 body make the series EDPS ideal for use with air and other noncombustible gases. The compact size, adjustment knob and meeting the UL508 standard make the EDPS the perfect choice for H.V.A.C. applications. Product Applications

  • Monitoring air filters and ventilators.
  • Monitoring industrial cooling-air circuits.
  • Overheating protection for fan heaters.
  • Monitoring flows in ventilation ducts.
  • Controlling air and fire-protection dampers.
  • Frost protection for heat exchanges

Dwyer EDPS-05-1-N Adjustable Differential Pressure Switch

 
 
Current Rating1.5 A
Model No.EDPS-05-1-N
Weight160 g
BrandDWYER
Temperature Limits-4 to 185degF
Pressure Limit10 kPa
Process Connection5/16″
Voltage250 VAC
Frequency50/60 Hz


The Series EDPS Adjustable Differential Pressure Switch is designed for pressure, vacuum, and differential pressures. The dual scaled adjustment knob in inches water column and pascals allows changes to the switching pressure to be made without a pressure gage. The EDPS is available with settings from 0.08″ w.c. (20 Pa) up to 16″ w.c. (4000 Pa). The silicone diaphragm and PA 6.6 body make the series EDPS ideal for use with air and other noncombustible gases. The compact size, adjustment knob and meeting the UL508 standard make the EDPS the perfect choice for H.V.A.C. applications. Product Applications

  • Monitoring air filters and ventilators.
  • Monitoring industrial cooling-air circuits.
  • Overheating protection for fan heaters.
  • Monitoring flows in ventilation ducts.
  • Controlling air and fire-protection dampers.
  • Frost protection for heat exchanges

Dwyer EDPS-06-1-N Adjustable Differential Pressure Switch

 
 
Current Rating1.5 A
Model No.EDPS-06-1-N
Weight160 g
BrandDWYER
Temperature Limits-4 to 185degF
Pressure Limit10 kPa
Process Connection5/16″
Voltage250 VAC
Frequency50/60 Hz

The Series EDPS Adjustable Differential Pressure Switch is designed for pressure, vacuum, and differential pressures. The dual scaled adjustment knob in inches water column and pascals allows changes to the switching pressure to be made without a pressure gage. The EDPS is available with settings from 0.08″ w.c. (20 Pa) up to 16″ w.c. (4000 Pa). The silicone diaphragm and PA 6.6 body make the series EDPS ideal for use with air and other noncombustible gases. The compact size, adjustment knob and meeting the UL508 standard make the EDPS the perfect choice for H.V.A.C. applications. Product Applications
  • Monitoring air filters and ventilators.
  • Monitoring industrial cooling-air circuits.
  • Overheating protection for fan heaters.
  • Monitoring flows in ventilation ducts.
  • Controlling air and fire-protection dampers.
  • Frost protection for heat exchanges
 

Dwyer EDPS-08-1-N Adjustable Differential Pressure Switch

 
 
Current Rating1.5 A
Model No.EDPS-08-1-N
Power/Voltage250 VAC
Weight160 g
BrandDWYER
Temperature Limits-4 to 185degF
Pressure Limit10 kPa
Process Connection5/16″
Frequency50/60 Hz

 

The Series EDPS Adjustable Differential Pressure Switch is designed for pressure, vacuum, and differential pressures. The dual scaled adjustment knob in inches water column and pascals allows changes to the switching pressure to be made without a pressure gage. The EDPS is available with settings from 0.08″ w.c. (20 Pa) up to 16″ w.c. (4000 Pa). The silicone diaphragm and PA 6.6 body make the series EDPS ideal for use with air and other noncombustible gases. The compact size, adjustment knob and meeting the UL508 standard make the EDPS the perfect choice for H.V.A.C. applications.


Product Applications:

  • Monitoring air filters and ventilators.
  • Monitoring industrial cooling-air circuits.
  • Overheating protection for fan heaters.
  • Monitoring flows in ventilation ducts.
  • Controlling air and fire-protection dampers.
  • Frost protection for heat exchanges

Dwyer EDPS-04-1-N Adjustable Differential Pressure Switch

 
 
Current Rating1.5 A
Model No.EDPS-04-1-N
Weight160 g
Temperature Limits-4 to 185degF
Pressure Limit10 kPa
Process Connection5/16″
Voltage250 VAC
Frequency50/60 Hz


The Series EDPS Adjustable Differential Pressure Switch is designed for pressure, vacuum, and differential pressures. The dual scaled adjustment knob in inches water column and pascals allows changes to the switching pressure to be made without a pressure gage. The EDPS is available with settings from 0.08″ w.c. (20 Pa) up to 16″ w.c. (4000 Pa). The silicone diaphragm and PA 6.6 body make the series EDPS ideal for use with air and other noncombustible gases. The compact size, adjustment knob and meeting the UL508 standard make the EDPS the perfect choice for H.V.A.C. applications. Product Applications

  • Monitoring air filters and ventilators.
  • Monitoring industrial cooling-air circuits.
  • Overheating protection for fan heaters.
  • Monitoring flows in ventilation ducts.
  • Controlling air and fire-protection dampers.
  • Frost protection for heat exchanges

Dwyer ADPS-07-2-N Adjustable Differential Pressure Switch

 
 
Current Rating1.5 A
Model No.ADPS-07-2-N
Power/Voltage250 VAC
Weight160 g
BrandDWYER
Temperature Limits-4 to 185degF
Pressure Limit10 kPa
Process Connection5/16″
Frequency50/60 Hz


Features:

  • Available with settings from 0.08″ w.c. (20 Pa) up to 16″ w.c. (4000 Pa)
  • The silicone diaphragm and PA 6.6 body make the series ADPS ideal for use with air and other noncombustible gases
  • The compact size, adjustment knob and low cost make the ADPS the perfect choice for HVAC applications


Specifications:

  • Service: Air and non-combustible, compatible gases
  • Temperature Limits: Process and ambient temperature from -4 to 185°F (-20 to 85°C)
  • Pressure Limits: Max. Operating Pressure: 40″ w.c. (10 kPa) for all pressure ranges
  • Switch Type: Single-pole double-throw (SPDT)
  • Electrical Rating: Max., 1.5A/250 VAC, max. switching rate: 6 cycles/min.; Gold Contact Option: 0.4 A/ 250 VAC
  • Electrical Connections: Push-on screw terminals. M20x1.5 with cable strain relief or optional 1/2″ NPT connection
  • Process Connections: 5/16″ (7.94 mm) outside diameter tubing, 1/4″ (6.0 mm) inside diameter tubing
  • Enclosure Rating: NEMA 13, IP54
  • Mounting Orientation: Vertically, with pressure connections pointing downwards
  • Mechanical Working Life: Over 106 switching operations
  • Weight: 5.6 oz (160 g)


Applications:

  • Monitoring air filters and ventilators
  • Monitoring industrial cooling-air circuits
  • Overheating protection for fan heaters
  • Monitoring flows in ventilation ducts
  • Controlling air and fire-protection dampers
  • Frost protection for heat exchanges

Dwyer EDPS-03-1-N Adjustable Differential Pressure Switch

 
 
Current Rating1.5 A
Model No.EDPS-03-2-N
Power/Voltage250 VAC
Weight160 g
BrandDWYER
Temperature Limits-4 to 185degF
Pressure Limit10 kPa
Process Connection5/16″
Frequency50/60 Hz

The Series EDPS Adjustable Differential Pressure Switch is designed for pressure, vacuum, and differential pressures. The dual scaled adjustment knob in inches water column and pascals allows changes to the switching pressure to be made without a pressure gage. The EDPS is available with settings from 0.08″ w.c. (20 Pa) up to 16″ w.c. (4000 Pa). The silicone diaphragm and PA 6.6 body make the series EDPS ideal for use with air and other noncombustible gases. The compact size, adjustment knob and meeting the UL508 standard make the EDPS the perfect choice for H.V.A.C. applications. Product Applications
  • Monitoring air filters and ventilators.
  • Monitoring industrial cooling-air circuits.
  • Overheating protection for fan heaters.
  • Monitoring flows in ventilation ducts.
  • Controlling air and fire-protection dampers.
  • Frost protection for heat exchanges
 

Dwyer ADPS-08-2-N Adjustable Differential Pressure Switch

 
 
Current Rating1.5 A
Model No.ADPS-08-2-N
Power/Voltage250 VAC
Weight160 g
BrandDWYER USA
Temperature Limits-4 to 185degF
Pressure Limit10 kPa
Process Connection5/16″
Frequency50/60 Hz


Features:

  • Available with settings from 0.08″ w.c. (20 Pa) up to 16″ w.c. (4000 Pa)
  • The silicone diaphragm and PA 6.6 body make the series ADPS ideal for use with air and other noncombustible gases
  • The compact size, adjustment knob and low cost make the ADPS the perfect choice for HVAC applications

Specifications

  • Service: Air and non-combustible, compatible gases
  • Temperature Limits: Process and ambient temperature from -4 to 185°F (-20 to 85°C)
  • Pressure Limits: Max. Operating Pressure: 40″ w.c. (10 kPa) for all pressure ranges
  • Switch Type: Single-pole double-throw (SPDT)
  • Electrical Rating: Max., 1.5A/250 VAC, max. switching rate: 6 cycles/min.; Gold Contact Option: 0.4 A/ 250 VAC
  • Electrical Connections: Push-on screw terminals. M20x1.5 with cable strain relief or optional 1/2″ NPT connection
  • Process Connections: 5/16″ (7.94 mm) outside diameter tubing, 1/4″ (6.0 mm) inside diameter tubing
  • Enclosure Rating: NEMA 13, IP54
  • Mounting Orientation: Vertically, with pressure connections pointing downwards
  • Mechanical Working Life: Over 106 switching operations
  • Weight: 5.6 oz (160 g)


Applications

  • Monitoring air filters and ventilators
  • Monitoring industrial cooling-air circuits
  • Overheating protection for fan heaters
  • Monitoring flows in ventilation ducts
  • Controlling air and fire-protection dampers
  • Frost protection for heat exchanges

Dwyer ADPS-06-2-N Adjustable Differential Pressure Switch

 
 
Current RatingMax. 1.5 A
Weight160 gm
Pressure Limit10 kPa
Enclosure RatingIP54
Voltage250 VAC
Frequency50/60 Hz


Features:

  • Available with settings from 0.08″ w.c. (20 Pa) up to 16″ w.c. (4000 Pa)
  • The silicone diaphragm and PA 6.6 body make the series ADPS ideal for use with air and other noncombustible gases
  • The compact size, adjustment knob and low cost make the ADPS the perfect choice for HVAC applications


Specifications:

  • Service: Air and non-combustible, compatible gases
  • Temperature Limits: Process and ambient temperature from -4 to 185°F (-20 to 85°C)
  • Pressure Limits: Max. Operating Pressure: 40″ w.c. (10 kPa) for all pressure ranges
  • Switch Type: Single-pole double-throw (SPDT)
  • Electrical Rating: Max., 1.5A/250 VAC, max. switching rate: 6 cycles/min.; Gold Contact Option: 0.4 A/ 250 VAC
  • Electrical Connections: Push-on screw terminals. M20x1.5 with cable strain relief or optional 1/2″ NPT connection
  • Process Connections: 5/16″ (7.94 mm) outside diameter tubing, 1/4″ (6.0 mm) inside diameter tubing
  • Enclosure Rating: NEMA 13, IP54
  • Mounting Orientation: Vertically, with pressure connections pointing downwards
  • Mechanical Working Life: Over 106 switching operations
  • Weight: 5.6 oz (160 g)


Applications:

  • Monitoring air filters and ventilators
  • Monitoring industrial cooling-air circuits
  • Overheating protection for fan heaters
  • Monitoring flows in ventilation ducts
  • Controlling air and fire-protection dampers
  • Frost protection for heat exchanges

Dwyer ADPS-04-2-N Adjustable Differential Pressure Switch

 
 
Current Rating1.5 A
Model No.ADPS-04-2N CA (18)
Power/Voltage250 VAC
Weight160 g
BrandDWYER
Temperature Limits-4 to 185degF
Pressure Limit10 kPa
Process Connection5/16″
Frequency50/60 Hz


Features:

  • Available with settings from 0.08″ w.c. (20 Pa) up to 16″ w.c. (4000 Pa)
  • The silicone diaphragm and PA 6.6 body make the series ADPS ideal for use with air and other noncombustible gases
  • The compact size, adjustment knob and low cost make the ADPS the perfect choice for HVAC applications


Specifications

  • Service: Air and non-combustible, compatible gases
  • Temperature Limits: Process and ambient temperature from -4 to 185°F (-20 to 85°C)
  • Pressure Limits: Max. Operating Pressure: 40″ w.c. (10 kPa) for all pressure ranges
  • Switch Type: Single-pole double-throw (SPDT)
  • Electrical Rating: Max., 1.5A/250 VAC, max. switching rate: 6 cycles/min.; Gold Contact Option: 0.4 A/ 250 VAC
  • Electrical Connections: Push-on screw terminals. M20x1.5 with cable strain relief or optional 1/2″ NPT connection
  • Process Connections: 5/16″ (7.94 mm) outside diameter tubing, 1/4″ (6.0 mm) inside diameter tubing
  • Enclosure Rating: NEMA 13, IP54
  • Mounting Orientation: Vertically, with pressure connections pointing downwards
  • Mechanical Working Life: Over 106 switching operations
  • Weight: 5.6 oz (160 g)


Applications

  • Monitoring air filters and ventilators
  • Monitoring industrial cooling-air circuits
  • Overheating protection for fan heaters
  • Monitoring flows in ventilation ducts
  • Controlling air and fire-protection dampers
  • Frost protection for heat exchanges

Dwyer ADPS-05-2-N Adjustable Differential Pressure Switch

 
 
Current Rating1.5 A
Model No.ADPS-05-2-N-CA (18)
Weight160 g
BrandDWYER
Temperature Limits-4 to 185degF
Pressure Limit10 kPa
Process Connection5/16″


Features:

  • Available with settings from 0.08″ w.c. (20 Pa) up to 16″ w.c. (4000 Pa)
  • The silicone diaphragm and PA 6.6 body make the series ADPS ideal for use with air and other noncombustible gases
  • The compact size, adjustment knob and low cost make the ADPS the perfect choice for HVAC applications

Specifications

  • Service: Air and non-combustible, compatible gases
  • Temperature Limits: Process and ambient temperature from -4 to 185°F (-20 to 85°C)
  • Pressure Limits: Max. Operating Pressure: 40″ w.c. (10 kPa) for all pressure ranges
  • Switch Type: Single-pole double-throw (SPDT)
  • Electrical Rating: Max., 1.5A/250 VAC, max. switching rate: 6 cycles/min.; Gold Contact Option: 0.4 A/ 250 VAC
  • Electrical Connections: Push-on screw terminals. M20x1.5 with cable strain relief or optional 1/2″ NPT connection
  • Process Connections: 5/16″ (7.94 mm) outside diameter tubing, 1/4″ (6.0 mm) inside diameter tubing
  • Enclosure Rating: NEMA 13, IP54
  • Mounting Orientation: Vertically, with pressure connections pointing downwards
  • Mechanical Working Life: Over 106 switching operations
  • Weight: 5.6 oz (160 g)


Applications:

  • Monitoring air filters and ventilators
  • Monitoring industrial cooling-air circuits
  • Overheating protection for fan heaters
  • Monitoring flows in ventilation ducts
  • Controlling air and fire-protection dampers
  • Frost protection for heat exchanges

Dwyer ADPS-03-2-N Adjustable Differential Pressure Switch

 
 
Current Rating1.5 A
Model No.ADPS-03-2-N CA (18)
Weight160 g
BrandDWYER
Temperature Limits-4 to 185degF
Pressure Limit10 kPa
Process Connection5/16″
Frequency50/60 Hz


Designed for pressure, vacuum, and differential pressures. The dual scaled adjustment knob in inches water column and Pascals allows changes to the switching pressure to be made without a pressure gage.

Adjustable differential pressure switch, set point range 0.20 to 2.00″ w.c., M20 connection.DPS Series Offers


Features

  • Available with settings from 0.08″ w.c. (20 Pa) up to 16″ w.c. (4000 Pa)
  • The silicone diaphragm and PA 6.6 body make the series ADPS ideal for use with air and other noncombustible gases
  • The compact size, adjustment knob and low cost make the ADPS the perfect choice for HVAC applications


Specifications

  • Service: Air and non-combustible, compatible gases
  • Temperature Limits: Process and ambient temperature from -4 to 185°F (-20 to 85°C)
  • Pressure Limits: Max. Operating Pressure: 40″ w.c. (10 kPa) for all pressure ranges
  • Switch Type: Single-pole double-throw (SPDT)
  • Electrical Rating: Max., 1.5A/250 VAC, max. switching rate: 6 cycles/min.; Gold Contact Option: 0.4 A/ 250 VAC
  • Electrical Connections: Push-on screw terminals. M20x1.5 with cable strain relief or optional 1/2″ NPT connection
  • Process Connections: 5/16″ (7.94 mm) outside diameter tubing, 1/4″ (6.0 mm) inside diameter tubing
  • Enclosure Rating: NEMA 13, IP54
  • Mounting Orientation: Vertically, with pressure connections pointing downwards
  • Mechanical Working Life: Over 106 switching operations
  • Weight: 5.6 oz (160 g)


Applications

  • Monitoring air filters and ventilators
  • Monitoring industrial cooling-air circuits
  • Overheating protection for fan heaters
  • Monitoring flows in ventilation ducts
  • Controlling air and fire-protection dampers
  • Frost protection for heat exchanges

Differential Pressure Switch

 
 
Minimum Order Quantity100 Number
Weight5.6 oz (160 g).
temperature LimitsProcess and ambient temperature from -4 to 185degF (-20 to 85degC).
Pressure LimitsMax. operating pressure: 40″ w.c. (10 kPa) for all pressure ranges.
Switch typeSingle-pole double-throw (SPDT).
Enclosure RatingNEMA 13 (IP54).
Process Connection” (6.0 mm) inside diameter tubing.s5/16″ (7.94 mm) outside diameter tubing, 1/4″ (6.0 mm) inside diameter tubing.


Being a market leader of this domain, we present clients with the premium quality of Differential Pressure Switch. Known for its simple calibration, digital push button and reduced set up time, the differential pressure switch is used for monitoring of air filters. Furthermore, the differential pressure switch is used for monitoring of ventilators.

Features:

  • Monitoring of industrial cooling air circuits
  • Simple calibration
  • Easy to use and maintain


Other Details:

  • Monitoring of air filters and ventilators
  • Monitoring of industrial cooling air circuits
  • Monitoring flow in ventilation ducts
  • Overheating protection in fan heaters
  • AHU status, fan status monitoring
  • Controlling air and fire-protection flaps
  • Frost protection for heat exchangers


Specifications:

  • Adjustable switching knob
  • Also available in ATEX, Hazardous area certified (Gr IIB, Gases)


Industries:

  • Clean rooms, pharmaceutical
  • Building ventilation
  • Fan status monitoring
  • Oil & gas
  • Food processing
  • Textile industries

Differential Pressure Switch DP930

 
 
Minimum Order Quantity12 Number
Model Name/NumberDP930
Power/Voltage1 SPDT,1A / 250VAC
Mounting TypeDiaphragm in Vertical Position
ProtectionIP54
Process Connection6.0mm Plastic Pipe
Housing MaterialABS
Repeatability+-2% of F.S
Temperature Ranges20 DegreeC to 85 DegreeC
Pressure RangesVarious Ranges upto 4 KPa

Special Features :
  • High Quality, Low-Cost
  • Visual Set Point Indication
  • Hassle-Free Field Adjustment Knob
  • 2% Repeatability

The DP930 Differential Pressure Switch is a low-cost easy to use switch for very low pressure applications. The switch can monitor positive, negative, or differential pressure and with an easy to adjust set point knob makes field set up and adjustment hassle free. The differential pressure switch includes a SPDT relay rated for 1A @ 250V and can be set as low as 0.08” w.c. (20 Pa)

 

Dwyer Air Filter Kit A – 481

 
 
Usage/ApplicationCommercial
MaterialPlastic
BrandDwyer
Packaging TypePacket
Length3 mtr


Dwyer Air Filter Kit A – 481

Mack – Dwyer USA

MODEL – 
A – 481 Installer Kit w/2 A-480 Plastic Static Tips and 6’ PVC Tubing

Sensocon USA Differential Pressure Switch Series 104 – 3

 
 
Model No.104-3
Electrical Rating2A @ 250 V
BrandSensocon
Max Pressure1000 Pa
Temperature Limit5dg to 140dgF
Repeatability2%
Process Connection3/16″


The Series 104 Differential Pressure Switch is a low-cost easy to use differential pressure switch for very low pressure applications. The differential pressure switch can monitor positive, negative, or differential pressure and with an easy to adjust set point knob makes field set up and adjustment hassle free. The differential pressure switch includes a SPDT relay rated for2A @ 250V and can be set as low as 0.08” w.c. (20 Pa).

Specification:

  • Media:Air and compatible gases
  • Max Pressure:20″ w.c. (5000 Pa)Temperature Limits:5 to 140°F (-15 to 60°C)Electrical Rating:2A @ 250 V
  • Electrical Connection:Screw terminals
  • Process Connection:3/16″ I.D. flexible tubing
  • Enclosure Rating:NEMA 13 (IP 54)Weight:3.5 oz (100 g)Accessories:6 ft (1.8m) flexible tubing, (2) Static pressure fittings, C type mounting bracket, and mounting screws
  • Repeatability:2%
  • Deadband:approximately 10% of max set point

Sensocon USA Differential Pressure Switch Series 104 – 0

 
 
BrandSensocon
Weight3.5 oz (100 g)
Electrical Rating2A @ 250 V
MediaAir and compatible gases
Max Pressure20″ w.c. (5000 Pa)
Temperature Limits5 to 140 DegreeF (-15 to 60 DegreeC)
Repeatability2%


The Series 104 Differential Pressure Switch is a low-cost easy to use differential pressure switch for very low pressure applications. The differential pressure switch can monitor positive, negative, or differential pressure and with an easy to adjust set point knob makes field set up and adjustment hassle free. The differential pressure switch includes a SPDT relay rated for2A @ 250V and can be set as low as 0.08” w.c. (20 Pa).

Specification:

  • Media:Air and compatible gases
  • Max Pressure:20″ w.c. (5000 Pa)Temperature Limits:5 to 140°F (-15 to 60°C)Electrical Rating:2A @ 250 V
  • Electrical Connection:Screw terminals
  • Process Connection:3/16″ I.D. flexible tubing
  • Enclosure Rating:NEMA 13 (IP 54)Weight:3.5 oz (100 g)Accessories:6 ft (1.8m) flexible tubing, (2) Static pressure fittings, C type mounting bracket, and mounting screws
  • Repeatability:2Þadband:approximately 10% of max set point

Sensocon USA Differential Pressure Switch Series 104 – 1

 
 
Model No.104-1
Weight173 gm
Electrical Rating2A @ 250 V
BrandSensocon
Repeatability2%
Max Pressure1000 Pa
Process Connection3/16″


The Series 104 Differential Pressure Switch is a low-cost easy to use differential pressure switch for very low pressure applications. The differential pressure switch can monitor positive, negative, or differential pressure and with an easy to adjust set point knob makes field set up and adjustment hassle free. The differential pressure switch includes a SPDT relay rated for2A @ 250V and can be set as low as 0.08” w.c. (20 Pa).

Specification:

  • Media:Air and compatible gases
  • Max Pressure:20″ w.c. (5000 Pa)Temperature Limits:5 to 140°F (-15 to 60°C)Electrical Rating:2A @ 250 V
  • Electrical Connection:Screw terminals
  • Process Connection:3/16″ I.D. flexible tubing
  • Enclosure Rating:NEMA 13 (IP 54)Weight:3.5 oz (100 g)Accessories:6 ft (1.8m) flexible tubing, (2) Static pressure fittings, C type mounting bracket, and mounting screws
  • Repeatability:2%
  • Deadband:approximately 10% of max set point

Sensocon USA Differential Pressure Switch Series 104 – 2

 
 
Model No.104-2
Weight3.5 oz (100 g)
Electrical Rating2A @ 250 V
BrandSensocon
MediaAir and compatible gases
Max Pressure20″ w.c. (5000 Pa)
Temperature Limits5 to 140 DegreeF (-15 to 60 DegreeC)
Repeatability2%

The Series 104 Differential Pressure Switch is a low-cost easy to use differential pressure switch for very low pressure applications. The differential pressure switch can monitor positive, negative, or differential pressure and with an easy to adjust set point knob makes field set up and adjustment hassle free. The differential pressure switch includes a SPDT relay rated for2A @ 250V and can be set as low as 0.08” w.c. (20 Pa).

Specification:
  • Media:Air and compatible gases
  • Max Pressure:20″ w.c. (5000 Pa)Temperature Limits:5 to 140°F (-15 to 60°C)Electrical Rating:2A @ 250 V
  • Electrical Connection:Screw terminals
  • Process Connection:3/16″ I.D. flexible tubing
  • Enclosure Rating:NEMA 13 (IP 54)Weight:3.5 oz (100 g)Accessories:6 ft (1.8m) flexible tubing, (2) Static pressure fittings, C type mounting bracket, and mounting screws
  • Repeatability:2%
  • Deadband:approximately 10% of max set point
 

Series 104 – Differential Pressure Switch

 
 
Media TypeAir and compatible gases
Model No.Series 104
Weight3.5 oz (100 g)
Electrical Rating2A @ 250 V
BrandSensocon
Max Pressure20″ w.c. (5000 Pa)
Temperature Limits5 to 140 DegreeF (-15 to 60 DegreeC)
Repeatability2%


The Series 104 Differential Pressure Switch is a low-cost easy to use switch
for very low pressure applications. The switch can monitor positive, negative,
or differential pressure and with an easy to adjust set point knob makes field
set up and adjustment hassle free. The differential pressure switch includes
a SPDT relay rated for 2A @ 250V and can be set as low as 0.08″ w.c. (20 Pa).